Product Description
Specs are as follows:
HLD Frame Style, Molded Case Circuit Breaker, LS Function Non-Interchangeable Trip Unit, 600 Ampere Max at 40 Degree Celsius, 3 Pole, 600VAC @ 50/60HZ, High Interrupting Capacity, Interrupting Ratings: 100 Kiloampere @ 240VAC, 65 Kiloampere @ 480VAC, 35 Kiloampere @ 600VAC, Rating Plug Not Included, Without Terminals Standard
L – Adjustable Long Delay Pickup (By Adjustable Rating Plug)
S – Adjustable Short Delay Pickup with Fixed Short Delay Time (I2t Response) or Adjustable Short Time (Flat Response)
ATTENTION: This unit requires a rating plug in order to function. Please contact us to check stock and pricing of rating plugs if you need one installed before ordering.
This product image represents a base model and is for identification purposes only. Are you purchasing accessories and your breaker in the same order? We will install your accessories to meet your specific configuration needs at NO ADDITIONAL COST! Just provide the necessary information in the order comment box during checkout.
Specifications
Manufacturer | Eaton / Cutler Hammer |
---|---|
Warranty | One Year |
Connection | Bolt On |
Frame Type | L |
Amperage | 600 Max |
Poles | 3 |
Voltage Max | 600 |
Interrupting Capacity Rating | 100 Kiloampere @ 240VAC, 65 Kiloampere @ 480VAC, 35 Kiloampere @ 600VAC |
Trip Setting | Adjustable 5-10 Times Continuous Ampere Rating |
Standard Lug Type | Without Terminals |