Product Description
Specs are as follows:
LDB Frame Style, Molded Case Circuit Breaker, LSI Function Non-Interchangeable Trip Unit, Suitable for Reverse Feed, 600 Ampere Max at 40 Degree Celsius, 3 Pole, 600VAC @ 50/60HZ, Interrupting Ratings: 65 Kiloampere @ 240VAC, 35 Kiloampere @ 480VAC, 25 Kiloampere @ 600VAC, 22 Kiloampere @ 250VDC, Rating Plug Not Included, Without Terminals Standard
L – Adjustable Long Delay Pickup (By Adjustable Rating Plug)
S – Adjustable Short Delay Pickup with Fixed Short Delay Time (I2t Response) or Adjustable Short Time (Flat Response)
I – Adjustable Instantaneous Pickup by Setting Short Time Delay Time to Instantaneous
ATTENTION: This unit requires a rating plug in order to function. Please give us a call or notate during checkout which rating plug you are needing before placing your order to ensure you receive a complete, working unit.
Below is a list of available rating plugs:
6LES300T / 6LES350T / 6LES400T / 6LES500T / 6LES600T / A6LES400T5 / A6LES500T5 / A6LES600T1
This product image represents a base model and is for identification purposes only. Are you purchasing accessories and your breaker in the same order? We will install your accessories to meet your specific configuration needs at NO ADDITIONAL COST! Just provide the necessary information in the order comment box during checkout.
Specifications
Manufacturer | Eaton / Cutler Hammer |
---|---|
Warranty | One Year |
Connection | Bolt On |
Frame Type | L |
Amperage | 600 Max |
Poles | 3 |
Voltage Max | 600 |
Interrupting Capacity Rating | 65 Kiloampere @ 240VAC, 35 Kiloampere @ 480VAC, 25 Kiloampere @ 600VAC, 22 Kiloampere @ 250VDC |
Trip Setting | Adjustable 5-10 Times Continuous Ampere Rating |
Standard Lug Type | Without Terminals |